ESIE09-05 Basic Control
Function 25
2.3 Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Furthermore, when outdoor temperature 20°C, the compressor will run in Step 7 or higher.
When outdoor temperature 18°C, it will run in Step 5 or higher.
When outdoor temperature 12°C, it will run in Step 1 or higher.
850 rpm
715 rpm
580 rpm
445 rpm
360 rpm
285 rpm
400 rpm
250 rpm
0 rpm
M1F
815 rpm
680 rpm
545 rpm
410 rpm
325 rpm
250 rpm
0 rpm
0 rpm
0 rpm
M2F
STEP3
STEP4
STEP5
STEP6
STEP7
STEP8
STEP2
STEP1
STEP0
Cooling
Fan Steps
Upper limit of fan
revolutions: Step 8
Upper limit of outdoor unit
fan revolutions
Step 7
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
Pc
<
2.75MPa
PI control
Pc
>
3.24MPa
Lapse of 20 sec.
PI control
PI control
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan
Pc: HP pressure sensor detection value
Все каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin ERQ and is the answer not in the manual?

Daikin ERQ Specifications

General IconGeneral
BrandDaikin
ModelERQ
CategoryHeat Pump
LanguageEnglish

Related product manuals