5.26.2 Heat recovery start-up and shut-down flowcharts
Heat recovery activation
Heat recovery pump
start
Recovery flow switch
consensus within timer
expiration
HR temperature control
start
No
HR Trip
Yes
HR temperature control
stabilitation
HR circuits activation
enabled
Control requires loading Control requires standby
Control requires
unloading
Loading interstage timer
expired
(PID calculation)
No
System standby
HR leaving temperature
above limit
No
HR 3Way valve
modulating
Yes
HR 3Way valve
complete opening
Unoading interstage
timer expired
(PID calculation)
Yes
New circuit activation
Yes
Last circuit deactivation
No