ESIE15-11A | Part 3. Field settings 7. Presence sensor BRYQ140A7 (for 3x3 cassette) / BRYQ60A7 (for 2x2 cassette)
Page 46 23/09/16
VRV4 indoor units
7. Presence sensor BRYQ140A7 (for 3x3 cassette) / BRYQ60A7 (for 2x2
cassette)
21 3 (for BRYQ60A7) Fanspeed setting during heating
operation
01 don’t speed up (correction factor 1,00)
02 speed up by 5% (correction factor 1,05)
03 speed up by 10% (correction factor 1,10)
6 Sensitivity presence sensor 01 high sensitive
02 low sensitive
03 standard
04 disable presence sensor
8 Compensation by floor sensor 01 floor sensor disabled
02 air suction temperature priority
03 standard
04 floor temperature priority
9 Compensation by floor temperature 01 -4°C
02 -2°C
03 no correction
04 +2°C
23 1 (for BRYQ60A7) Select airflow direction 01 4-way direction
02 3-way direction