ESIE15-11A | Part 3. Field settings 3. Wired remote controller BRC1D51/52
Page 28 23/09/16
VRV4 indoor units
3.2. Field settings, specific for BRC1D51/52
Mode
No.
Note 1
FIRST
CODE
NO.
Description of setting
SECOND CODE NO. Note 2
01 02 03 04
10(20) 0 Filter Contamination - Heavy/Light
(Setting for spacing time of display
time to clean air filter) (Setting for
when filter contamination is heavy,
and spacing time of display time to
clean air filter is to be halved)
Ultra long
life filter
Light
Approx.
10.000
hrs.
Heavy
Approx.
5.000
hrs.
--
Long life
filter
Approx.
2.500
hrs.
Approx.
1.250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1 Long-life filter type (setting of filter sign indication
time). (Change setting when ultra-long filter is
installed)
Long-life
filter
Ultra-long
life filter
--
2 Thermostat sensor in remote controller Use Not use - -
3 Spacing time of display time to clean air filter
count (setting for when the filter sign is not to be
displayed)
Display Do not
display
--
12(22) 1 ON/OFF input from outside (setting for when
forced ON/OFF is to be operated from outside).
Forced OFF ON/OFF
operation
--
2 Thermostat differential changeover (setting for
when using remote sensor).
1°C 0,5°C - -
13(23) 0 High air outlet velocity (for high ceiling applica-
tions).
2,7 m >2,73,0 m >3,03,5 m -
1 Selection of air flow direction (setting for when a
blocking pad kit has been installed).
4-way flow 3-way flow 2-way flow -
3 Selection of air flow function (setting for when
using a decoration panel for outlet).
Equipped Not
equipped
--
4 Air flow direction range setting. Upper Normal Lower -
6 Setting the external static pressure (setting
according to the connected duct resistance)
(for FHYK, follow the high ceiling setting)
Normal
(Normal)
High static
pressure
(High
ceiling)
Low static
pressure
-
-
15(25) 3 Drain pump operation with humidifying. Equipped Not
equipped
--
1b 0 Permission level setting Level 2 Level 3 - -
1 Leave home function Not
permitted
Permitted - -
2 Thermostat sensor in remote controller (for limit
operation and leave home function only)
Use Not use - -