10.8.17 Maximum Number of Restart Alarm (condenserless units only)
This alarm indicates that for three consecutive times after the compressor start the evaporating pressure is under a
minimum limit for too much time
Symptom
Solution
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
String in the alarm list:
Cx OffNbrRestarts
String in the alarm log:
Cx OffNbrRestarts
String in the alarm snapshot
Cx OffNbrRestarts
Check the operating envelope for this
machine.
Reset
Notes
Local HMI
Network
Auto
10.9 Circuit Pumpdown Stop Alarms
10.9.1 Low Discharge Superheat Fault
This alarm indicates that the unit has worked for too long with low discharge super heat.
Symptom
Cause
Circuit status is Off.
The circuit is switched off with the
shutdown procedure.
Bell icon is moving on controller’s
display. String in the alarm list:
CxCmp1 OffDishSHLo
String in the alarm log:
CxCmp1 OffDishSHLo
String in the alarm snapshot
CxCmp1 OffDishSHLo
EEXV is not working correctly.
It’s not opening enough or it’s moving
in the opposite direction.
Reset
Local HMI
Network
Auto

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals