Instructions Unit installation
5
VIEWA402
Wall Air units instructions w
1
& w
2
Place the wall mounting bracket on wall in
desired position, 75 mm from the bottom of the
bracket to the top of the unit, mark up- and drill
holes. Use screws suitable for the wall surface
(screws are not included).
Very important!
Ensure that the bracket is level.
Now hang unit onto wall
bracket, attach self-adhesive
foam blocks to lower rear
location on unit back plate
(absorbs potential vibrations
from unit to wall). Mount the siphon on the wall
below the unit.
Now fit the pipe from the siphon onto the sys-
tems condensate connector using the attached
pipe clip. The condensate is led from the siphon
on to the nearest outlet with a gradient of min.
1cm/metre. The condensate line must be insu-
lated where risk of freezing occurs.
Important: Remove front panel, and foam front
panel. Fill condensate tray, check the outlet and
reassemble.
75 mm
+
Rubber
separator
A
Detail A
Wall unit Top view
Condensate con-
nection
located here
(below unit)
Important
Allow for 60 cm
free space in
front of unit, to
assure service
access.