User Guide | Controller for appliance control, AK-CC 450
RS8EU702 | 23
© Danfoss | ADAP-KOOL® | 2015.10
Conguration of the alarm relay
The alarm relay will be activated upon an alarm signal from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input is activated for alarm
16 - Defrost alarms
32 - Miscellaneous
The groups that are to activate the alarm relay must be set by using a numerical value
which is the sum of the groups that must be activated.
(E.g. a value of 5 will activate all high temperature alarms and all sensor errors. 0 will cancel
the relay function)
P41 Al.Rel. Conf.
Service Service
Temperature measured with S5 sensor u09 S5 temp.
Status on DI1 input. on/1=closed u10 DI1 status
Read the duration of the ongoing defrost or the duration of the last completed defrost. u11 Defrost time
Temperature measured with S3 sensor u12 S3 air temp
Status at the day-/night operation (night operation: on/o) u13 Night Cond.
Temperature measured with S4 sensor u16 S4 air temp
Thermostat temperature u17 Ther. air
Read the ongoing cutin time for the thermostat or the duration of the last completed
cutin
u18 Ther runtime
Read the temperature at the S6 sensor u36 S6 temp
Status on DI2 output. on/1=closed
u37 DI2 status
Air temperature. Weighted S3 +S4
u56 Display air
Measured temperature for alarm thermostat
u57 Alarm air
Status on relay for cooling
u58 Comp1/LLSV
Status on relay for fan
u59 Fan relay
Status on relay for defrost
u60 Def. relay
Status on relay for railheat
u61 Railh. relay
Status on relay for alarm
u62 Alarm relay
Status on relay for light
u63 Light relay
Status on relay for valve in suction line
u64 SuctionValve
Status on relay for compressor 2
u67 Comp2 relay
Temperature measured with S5B sensor
u75 S5 temp. B
Temperature measured with S3B sensor
u76 S3 airtemp B
Temperature measured with S6B sensor
u79 S6 temp. B
Status on relay for hot gas
u80 Hotgas valve
Status on relay for heating element in drip tray
u81 Drip tray
Status on relay for night blinds
u82 Blinds relay
Status on relay for defrost B
u83 Def. relay B
Status on relay for heat function
u84 Heat relay
Readout of the actual rail heat eect in %
u85 Rail DutyC %
Readout of which thermostat used for regulation: 1= Thermostat 1,
2= Thermostat 2
u86 Ther. band
Status on input DI3 (on/1 = 230 V)
u87 DI3 status
Readout of the actual cutin value for the thermostat
u90 Cutin temp.
Readout of the actual cut out value for the thermostat
u91 Cutout temp.
Readout of the actual Brine PWM OD in %
U02 Pwm OD %
Forced control
If you need to force-control an output, you should set r12 to -1 (manual mode). You should then select the relevant relay function, e.g. u58. Go
to the function by pressing the middle button. Select On.