Glossary
EY.65.H4.02
91
PI controller Proportional-integral controller. This is the method or algorithm that the ECL 2000
uses to control temperature. A PI controller combines:
A proportional controller, which provides fast control ensuring that the
controller’s output signal is proportional to the measured process variable. The
effect of the proportional controller is determined by the parameter amplification
or proportional band.
An integral controller, which helps remove any constant deviation of the process
variable from the desired value (the setpoint). The parameter integration time
determines the effect of the integral controller.
Pt 1000 Temperature dependent resistance: 1000
at 0 °C. The resistance varies by
approximately 3.8
/K.
Room influence This facility allows the controller to reduce or increase the flow temperature in a heat
circuit if the room temperature exceeds a user-defined maximum or minimum.
Service settings The service settings are a number of parameters that determine how the ECL 2000
functions. The service settings can be displayed and modified via the controller’s
service menu.
Stand-by In this operating mode, automatic control of heat and hot-water circuits is disabled.
However, the controller constantly monitors the flow temperature in the circuits.
Should the flow temperature drop below 6 °C, the controller activates heating in order
to avoid frost damage.
Summer cut-off This facility enables the controller to close down a heat circuit when the outdoor or
room temperature exceeds a user-defined level.
Timer The ECL 2000’s timer function enables the controller to switch on and off some
external device, according to a user-defined 7-day, 24-hour plan.
Weather compensation A facility that enables the controller to take outdoor weather conditions into
consideration for heat circuit control. In the ECL 2000, this facility is based on a user-
definable weather compensation curve which determines what the flow temperature
should be when the outdoor temperature varies. It is possible to set up weather
compensation curves for flow and return temperatures in heat circuits.

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals