16 Manual RS8EE202 © Danfoss 08-2010 EKC 202D
Light-emitting diodes (LED) on front panel
The other LED’s on the front panel will light up when the belong-
ing relay is activated.
= Refrigeration
= Defrost
= Fan running
The light-emitting diodes will ash when there is an alarm.
In this situation you can download the error code to the display
and cancel/sign for the alarm by giving the top knob a brief push.
Defrosting
A “-d-” is appears in the display during defrosting. This display will
appear for up to 15 minutes after cooling resumes.
However, the “-d-” display does not apply if:
- Temperature is reached within 15 minutes.
- Regulation is stopped via the “Main Switch.
- A high temperature alarm is activated.
The buttons
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the col-
umn with parameter codes. Find the parameter code you want to
change and push the middle buttons until value for the parameter
is shown. When you have changed the value, save the new value
by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and nd that parameter you
want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.
Display
The values will be shown with three digits, and with a setting you
can determine whether the temperature are to be shown in °C or
in °F.
Operation
Get a good start
With the following procedure you can start regulation very quick-
ly:
1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means
stopped regulation.)
2 Select electric connection based on the drawings on page 6
3 Open parameter o61 and set the electric connection number in
it
4 Open parameter r12 and start the regulation
5 Go through the survey of factory settings. The values in the grey
cells are changed according to your choice of settings. Make any
necessary changes in the respective parameters.
6 For network. Set the address in o03 and then transmit it to the
gateway/system unit with setting o04.
Cutout alarm relay / receipt alarm/see alarm code
• Push short the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan the rolling
stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor
• Push short the lower button
Manuel start or stop of a defrost
• Push the lower button for four seconds.