Survey of functions
Function Para-
meter
Parameter by operation via data
communication
Normal display
Normally the temperature value from one of the two thermostat sensors S3 or S4 or a
mixture of the two measurements is displayed.
In o17 the ratio is determined.
Display air (u56)
Thermostat Thermostat control
Set point
Regulation is based on the set value plus a displacement, if applicable. The value is set
via a push on the centre button.
The set value can be locked or limited to a range with the settings in r02 and r 03.
The reference at any time can be seen in ”u28 Temp. ref”
Cutout °C
Differential
When the temperaure is higher than the reference + the set dierential, the compres-
sor relay will be cut in. It will cut out again when the temperature comes down to the
set reference.
r01 Dierential
Setpoint limitation
The controller’s setting range for the setpoint may be narrowed down, so that much
too high or much too low values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. allowable reference value must
be lowered.
r02 Max cutout °C
To avoid a too low setting of the setpoint, the min. allowable reference value must be
increased.
r03 Min cutout °C
Correction of the display’s temperature showing
If the temperature at the products and the temperature received by the controller are
not identical, an oset adjustment of the shown display temperature can be carried
out.
r04 Disp. Adj. K
Temperature unit
Set here if the controller is to show temperature values in °C or in °F.
r05 Temp. unit
°C=0. / °F=1
(Only °C on AKM, whatever the set-
ting)
Correction of signal from S4
Compensation possibility through long sensor cable
r09 Adjust S4
Correction of signal from S3
Compensation possibility through long sensor cable
r10 Adjust S3
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or a manual override of the
outputs can be allowed.
Start / stop of refrigeration can also be accomplished with the external switch func-
tion connected to a DI input.
Stopped refrigeration will give a ”Standby alarm”.
r12 Main Switch
1: Start
0: Stop
-1: Manual control of outputs allowed
Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller
changes over to night operation. (Select a negative value if there is to be cold ac-
cumulation.)
r13 Night oset
Selection of thermostat sensor
Here you dene the sensor the thermostat is to use for its control function. S3, S4, or a
combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
r15 Ther. S4 %
Activation of reference displacement
When the function is changed to ON the thermostat dierential will be increased by
the value in r40. Activation can also take place via input DI1 or DI2 (dened in o02 or
o37).
r39 Th. oset
Ref. Dif.