2 Manual RS8FM602 © Danfoss 02-2016 EKC 326A
Introduction
Application
The controller can be used in systems with transcritical and sub-
critical cooling control systems where CO2 is used as a refrigerant.
The controller regulates the pressure in the gas cooler (condens-
er) so that the system achieves the optimal COP.
The controller covers the following:
Transcritical CO2 refrigeration systems (booster, cascade, high
pressure)
Transcritical CO2 heat pump systems
Transcritical CO2 refrigeration systems with heat recovery
Transcritical CO2 chiller systems
• Extra capacity in warm periods. An improvement in the system’s
cooling performance can be achieved by displacement of the
set point (“extra compressor")
Advantages
Maximum COP
The controller guarantees the systems maximum performance
by maintaining the optimal pressure in the gas cooler when
regulation takes place in the transcritical range.
The controller will always optimise to a subcritical state.
• Regulating the receiver pressure based on the receiver pressure
reading
• Heat recovery with adjustable reference pressure, 0-10 V
• Optimum heat pump operation
System
The pressure in the gas cooler is controlled by the valve. Regula-
tion must have inputs from both a pressure transmitter PGC and
a temperature sensor SGC. Both must be tted in the outlet im-
mediately after the gas cooler.
The valve is an ICMTS valve, which has been specially developed
for the pressure conditions that exist in a transcritical CO
2
system.
The motor section of the valve is an ICAD actuator and is control-
led by a 0-10 V signal from the controller.
If it is necessary to maintain a constant receiver pressure, a valve
(ETS, CCM or CCMT) and pressure transmitter (Prec) can be in-
stalled. The gas from the receiver bypasses to the inlet side of the
high pressure compressor.
Functions
Maximum COP control
The controller maintains optimum pressure in the transcritical
range based on a pressure and temperature reading.
The reference line is dened with a point at 100 bar. The desired
temperature can be set here.
Subcooling
d T subcooling can be used in the subcritical range.
Contents
Introduction ....................................................................................................... 2
Examples ............................................................................................................. 4
Survey of functions .......................................................................................... 6
Operation ..........................................................................................................10
Menu survey .....................................................................................................10
Connections .....................................................................................................11
Data .....................................................................................................................13
Ordering ............................................................................................................13
Appendix ........................................................................................................... 14

Other manuals for Danfoss EKC 326A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 326A and is the answer not in the manual?

Danfoss EKC 326A Specifications

General IconGeneral
BrandDanfoss
ModelEKC 326A
CategoryController
LanguageEnglish

Related product manuals