FC 300 Instruction Manual
General Specifications
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heat sink ensures that adjustable frequency drive the trips if the
temperature reaches 203 °F ± 9 °F (95 °C ± 5 °C). An overload temperature cannot be reset until
the temperature of the heat sink is below 158 °F ± 9 °F (70 °C ± 5 °C).
The adjustable frequency drive is protected against short circuits on motor terminals U, V, W.
If a mains phase is missing, the adjustable frequency drive trips or issues a warning.
Monitoring of the i ntermediate circuit voltage e nsures that the adjustable frequency drive
trips if the intermediate circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
66