FC 300 Instruction Manual
How to Install
" Electrical Installation
" Connection to M ains and Grounding
NOTE
The plug connector for p ower can
be removed.
1. Make sure the FC 300 is properly grounded.
Connect to ground connection (terminal 95).
Use screw from the accessory bag.
2. Place plug connec tor 91, 92, 93 from the
accessory bag onto the terminals labele d
MAINS at the bottom of FC 30 0.
3. Connect mains wires to the mains
plug connector.
The ground connection cable cross-section
must be at least 0.015 in.
2
(10 mm
2
)or2
rated mains wires terminated separately.
How to connect to mains and grounding.
NOTE
Check that mains voltage cor
responds
to the mains voltag e of the FC
300 nam ep late .
Do not connect 400-V uni
ts with
RFI-filters to elec trical supplies with a
voltage between phase and ground of
more than 440 V. For
IT AC line and delta ground
(grounded leg), AC line voltage may exceed
440 V between phase and ground.
Terminals for e lectrical source and ground ing.
15