EasyManuals Logo
Home>Danfoss>Controller>Icon2

Danfoss Icon2 User Manual

Danfoss Icon2
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
42 | © Copyright Danfoss Climate Solutions | 2023.01
AB432956914381en-010101
Service Manual Danfoss Icon2™
Application 10 Continued
Installer App settings
Function Factory setting
Off On
PWM+ proportional control of actuator outputs
Heat pump optimizer – maintenance of minimum flow
Dead band heating/cooling changeover 4K
Time delay for changeover to cooling mode 6h
Required accessories
1 2-way control valve RA-C DN20 013G3096
Compression ferrule set 22mm x 1" for RA-C 20 013U0135 (x8)
2 Stainless steel floor heating manifold SSM-F, 2–12 groups
088U0752 to
088U0762
Set of 2 mounting brackets 088U0585
Set of 2 ball valves 1" 088U0822
3 Thermal actuator TWA-A 230V NC suitable for SSM-F manifold 088H3112
4 Dew point sensor CF-DS 088U0251
5/6 Thermal actuator TWA-A 230V NC suitable for RA-C DN20 088H3112 (x4)
Explanation of heating and cooling for end user
No cooling will occur
until the reference room temperature has exceeded the set
temperature + set dead band for longer than the set time delay. For example, after the
rooms temperature has been over 25°C (21°C + 4K) for six hours.
The rooms temperature will never be cooled further than 2 degrees above the set
temperature. If the temperature is set to 21°C, for example, the room will be cooled
to 23°C. Heating will activate as soon as the room temperature drops below the set
temperature.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Icon2 and is the answer not in the manual?

Danfoss Icon2 Specifications

General IconGeneral
BrandDanfoss
ModelIcon2
CategoryController
LanguageEnglish

Related product manuals