46 | © Copyright Danfoss Climate Solutions | 2023.01
AB432956914381en-010101
Service Manual Danfoss Icon2™
Application 11 Continued
Installer App settings
Function Factory setting
Off On
PWM+ proportional control of actuator outputs
Heat pump optimizer – maintenance of minimum flow
PWR1 switch-on delay of 3 minutes
Dead band heating/cooling changeover 4K
Time delay for changeover to cooling mode 6h
Heating supply temperature 40.0°C
Cooling supply temperature 18.0°C
Heating safety temperature 50.0°C
Cooling safety temperature 17.0°C
Required accessories
1 6-way ball valve ChangeOver6 DN20 003Z3151
2 Actuator 230V suitable for ChangeOver6 DN20 003Z3154
3 2-way control valve with flow regulator AB-QM DN20 003Z8203
Thermal actuator TWA-Q 24V NC suitable for AB-QM DN20 082F1602
Threaded fittings R3/4" suitable for AB-QM DN20 003Z0233 (x2)
4 Stainless steel floor heating manifold SSM-F, 2–12 groups
088U0752 to
088U0762
Set of 2 mounting brackets 088U0585
Set of 2 ball valves 1" 088U0822
5 PT1000 temperature sensor ESM-11 087B1165
6 Dew point sensor CF-DS 088U0251
7 Thermal actuator TWA-A 230V NC suitable for SSM-F manifold 088H3112
8 “Circulation pump Wilo Para 15-130/6” 145H4269
9 Heat exchanger XB06H-1-26 145H3671
Explanation of heating and cooling for end user
No cooling will occur
until the reference room temperature has exceeded the set
temperature + set dead band for longer than the set time delay. For example, after the
room’s temperature has been over 25°C (21°C + 4K) for six hours.
The room’s temperature will never be cooled further than 2 degrees above the set
temperature. If the temperature is set to 21°C, for example, the room will be cooled
to 23°C. Heating will activate as soon as the room temperature drops below the set
temperature.