Level 2 - Programming (Installer Level)
To access the second programming level press the
UP () and DOWN () keys and the LIGHT key
simultaneously for a few seconds.
When the rst programming variable appears the
system automatically goes to stand-by.
1. Select the variable to be modied by pressing the
UP () and DOWN () keys.
When the parameter has been selected it is
possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down
and pressing the () or () key.
4. When conguration settings have been
completed you can exit the menu by pressing the
() and () keys simultaneously and keep them
pressed until the room temperature reappears.
5. Changes are saved automatically when you exit
the conguration menu.
6. Press the STAND-BY key to enable electronic
control.
List of Level 2 variables (Installer Level)
Variables Explanation Value Default
AC Door switch status 0 = normally open
1 = normally closed
0
F3 Fan status with compressor o 0 = fans run continuously
1 = fans only run when
compressor is working
1
F4 Fan pause during defrost 0 = fans run during defrost
1 = fans do not run during defrost
1
dE Sensor presence
If the evaporator sensor is disabled defrosts are
carried out cyclically with period d0: defrosting
ends when an external device trips and closes the
remote defrost contact or when time d3 expires.
0 = evaporator sensor present
1 = no evaporator sensor
0
d1 Defrost type, cycle inversion (hot gas) or with
heater elements
1 = hot gas
0 = electric
0
bdr Modbus baudrate
(Danfoss System unit =19200 baud)
0=300. 1=600. 2=1200. 3=2400.
4=4800. 5=9600. 6=14400.
7=19200. 8=38400 baud.
7
Ad Modbus address 1 ... 247
(+ setting: AU must be set to 7)
(+ move jumper: see page 14)
0
Ald Minimum and maximum temperature
Signalling and alarm display delay
1…240 min 120 min
C1 Minimum time between shutdown and
subsequent switching on of the compressor.
0…15 min 0 min
CAL Correction of sensor signal -10…+10 0
Pc Compressor protection contact status 0 = NO
1 = NC
0 = NO
doC Compressor safety time for door switch: when
the door is opened the evaporator fans shut down
and the compressor will continue working for time
doC, after which it will shut down.
0…5 minutes 0
tdo Restart time, if the door remains open 0... 240 min. (0=no function) 0
Fst FAN shutdown TEMPERATURE
The fans will stop if the temperature value read by
the evaporator sensor exceeds this value.
-45…+45°C +45°C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss OPTYMA Control AK-RC 101 and is the answer not in the manual?

Danfoss OPTYMA Control AK-RC 101 Specifications

General IconGeneral
BrandDanfoss
ModelOPTYMA Control AK-RC 101
CategoryControl Panel
LanguageEnglish

Related product manuals