Section 1 Section 2 Section 3
How to program
The Quick Setup shown is based on the assumption
that you want your VLT to operate with the following
setup:
1. External start/stop
2. Potentiometer connected for external speed control
3. Option to change rotation direction
4. Option to select a fixed speed (Jog)
If you use a brake module, you must program
one parameter more, and two more if you
want local operation via the display keys.
This will appear from the two tables at the bottom.
To store the data press the “menu” key!
When you have connected your VLT, as described on
the previous page, you must program a few parame-
eters.
Perform steps 1-9 for Quick Setup.
After installation
Standard motor with constant torque load without brake module on the frequency converter
Step Parameter Designation Settings Display indication
1 000 Language Choose English ENGLISH
2 103 Motor power Read motor plate
3 104 Motor voltage Read motor plate
4 105 Motor frequency Read motor plate
5 201 Min. frequency Set wanted frequency
6 202 Max. frequency Set wanted frequency
7 215 Ramp up 1 Set wanted ramping time
8 216 Ramp down 1 Set wanted ramping time
9 Start This is done by supplying terminals 18 and 27
the frequency with 24 V DC from the frequency converter’s terminal 12
converter or by using an external 24 V DC voltage
If a brake module is mounted, make the following settings
Step Parameter Designation Settings Display indication
1 300 Brake function If a brake module is used, choose Applied APPLIED
2 Start This is done by supplying terminals 18 and 27
the frequency with 24 V DC from the frequency converter’s terminal 12,
converter or by using an external 24 V DC voltage
If you want local operation and start, make the following settings
Step Parameter Designation Settings Display indication
1 003 Operation site Choose Local LOCAL
2 004 Local reference Record wanted output frequency by means
of the “+” and “” keys