FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
Switch 1 2 3 4 5 6 7 8
Address Switch setting
0 OFF OFF OFF OFF OFF OFF OFF X
1 ON OFF OFF OFF OFF OFF OFF X
2 OFF ON OFF OFF OFF OFF OFF X
....125 ON ON ON ON ON OFF ON X
126 ON ON ON ON ON ON OFF X
127
(default)
ON ON ON ON ON ON ON X
FCD 300 LEDs
The bus LED on the front:
LCP stop mode or
Operation site = local
Remote and bus control
Baud rate search LED is flashin g LED is flashing
Baud rate found and drive is ready
to get and set cyclical data
Flashing 1.5 sec. On
Baud rate found and drive is not
set to state receive/send cyclic al
data
Flashing 1.5 sec. Flashing: 2 sec. off, 320 ms on
Only acyclical communication (no
cyclical data)
Flashing 1.5 sec. Flashing: 2 sec. off, 320 ms on
In case that a cyclical communication is established,
the LED is on. If o nly a acyclical communication with
a master 2 is active the LED is flashi ng.