Page #128 background imageLoading...
Page #128 background image
127MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
EXCEPT
XXXX ERROR
PC=XXXX
Display messages
Alarm messages
(continued)
If disabled keypad is pressed:
KEY DISABLED
Indicates factory setup.
Change parameter 001 to setup 1-4.
Or the key is disabled (parameters
006-009).
If data change only possible when the
frequency converter is stopped is
attempted: ONLY ON STOP
If data change is attempted with open
LOCK-switch: PROG.LOCKED
If data change is attempted out of
allowed range: LIMIT
Error messages
Auto optimization ok (TUNING OK):
Auto optimization has taken place.
Auto optimization fault
(TUNING. FAULT): Fault code 13
The reasons for auto optimization fault can
be the following:
The connected motor is very small or very
large in relation to the VLT
®
frequency
converter.
The motor is loaded more than 50%.
The connected motor is a special motor,
e.g. a synchronous motor.
The fault can be due to electrical noise,
e.g. no or poor earth connection to the
VLT
®
frequency converter.
The reason can also be attempts at auto
optimization on a very small motor in relation
to the VLT
®
frequency converter (5-6
undersizes).
The VLT
®
frequency converter performs a
self-test of the control card when the mains
voltage is connected, giving the following
message:
The reason for the fault message is a fault
on the control card or possible option card.
Contact Danfoss.
TESTING
CONTROL CARD
FAULT_XXXX
EXCEPT fault::
Start-up test:
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for Danfoss VLT 3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3000 Series and is the answer not in the manual?

Danfoss VLT 3000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3000 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals