EasyManuals Logo
Home>Danfoss>Media Converter>VLT 3000 Series

Danfoss VLT 3000 Series User Manual

Danfoss VLT 3000 Series
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
60 MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
The control panel for programming and
local control and information is placed on
the front of the frequency converter.
The control panel consists of a keyboard
and a display.
The keyboard is used for two purposes:
local operation and programming.
The display is used for communication
between the frequency converter and
the operator.
On the control panel you will see a red
and a green LED.
When the green LED (On) lights up, there is
voltage to the frequency converter.
The red LED (Alarm) is used for alarm
indications.
In an ALARM MODE the LED will flash.
Using an optional adaptor and cable, the
control panel can be mounted in a cabinet
cover. The maximum distance between the
frequency converter and the remote box is 3
m.
The enclosure of the adapter (front) is IP 54.
Minimum panel aperture: 112 x 51 mm
± 0.5 mm.
The control panel
Keys for programming
Programming is carried out by changing
the data values of parameters grouped in
a menu.
Some parameters can have different
settings in four separate setup functions
(parameter 001). See p. 81 for more
information. is used to find (select) the
parameter to be changed.
Menu
is used to enter MENU MODE from
either DATA MODE or DISPLAY MODE.
Menu
is also used to enter a specific group of
parameters.
Data
is used to enter DATA MODE or DIS-
PLAY MODE from MENU MODE.
Data
is
also used to move the cursor between data
values.
+
and
are used to select a group of
parameters, a specific parameter or a data
value.
From any status you can enter DISPLAY
MODE by pressing
Menu
and
Data
at the same
time.
Menu
Data
+
External mounting
of the control panel
(remote box)
In normal operation (in DISPLAY MODE)
+
and
are used to scroll between 12 dis-
play read-outs:
Reference %
Frequency Hz
Display / Feedback %
Current A
Torque %
Power kW
Power HP
Energy kWh
Motor voltage V
D.C. voltage V
Motor load therm. %
Inverter load therm %
Parameters 003/004 are used for local
reference setting.
Jog
is used to run the motor at a fixed pre-
programmed frequency (parameter 203).
Fwd.
Rev.
is used to change direction.
Note: For safety reasons the key can only
be activated when the frequency converter
is set for local operation (parameter 003),
and the functions
Jog
and
Fwd.
Rev.
must be se-
lected in parameters 008 and 009.
Keys for local operation
Start
Stop
Reset
Fwd.
Rev.
Jog
+
Control panel
Menu
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for Danfoss VLT 3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3000 Series and is the answer not in the manual?

Danfoss VLT 3000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3000 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals