23MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains supply 3 x 200/220/230 V and 3 x 220/230/240 V Technical data
According to international VDE and UL/CSA requirements VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Constant torque (CT):
Output current I
VLT,N
[A] 5.4 7.8 10.5 19.0 25.0 32.0 46.0 61.0 80.0 104.0 130.0
I
VLT,MAX
[A] (60 s) 6.7 12.5 17.0 30.0 40.0 51.2 73.6 97.6 120.0 156.0 195.0
Output S
VLT,N
[kVA] 2.1 3.1 4.2 7.6 10.0 12.7 18.3 24.3 31.9 41.4 51.8
S
VLT,MAX
[kVA] (60 s) 2.7 4.9 6.7 12.0 15.9 20.4 29.2 38.9 47.8 62.1 77.7
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 4.0 5.5 7.5 11.0 15.0 22.0 30.0 37.0
Quadratic torque (VT):
Output current I
VLT,N
[A] 5.4 7.8 10.5 25.0 32.0 46.0 61.0 88.0 104.0 130.0 154.0
Output S
VLT,N
[kVA] 1.9 2.9 4.0 10.0 12.7 18.3 24.3 35.1 41.4 51.8 61.3
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 5.5 7.5 11,0 15,0 22.0 33.0 37.0 45.0
Max. cable cross-section [mm
2
] 2.5 2.5 2.5 16.0 16.0 16.0 35.0 50.0 70.0 70.0 70.0
Max. motor cable length [m] 300, with screened cables: 150 m 300
Output voltage U
M
[%] 0-100, of mains voltage max. 230 V
Output frequency f
M
[Hz] 0-120 or 0-500; programmable
Rated motor voltage U
M,N
[V] 200/220/230
Rated motor frequency f
M,N
[Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic);
thermistor to DIN 44081
Switching on output Unlimited (frequent switching on output may result
in fault message)
Ramp times [s] 0.1 - 3600
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Max. input current const. load I
L,N
[A] 6.8 9.1 13.3 17.5 22.2 26.4 41.7 52.2 78.0 102.0 128.0
quad. load I
L,N
[A] 6.8 9.1 13.3 23.1 29.6 42.0 56.8 72.3 102.0 128.0 152.0
Max. cable cross-section [mm
2
] 2.5 2.5 2.5 16.0 16.0 16.0 35.0 50.0 120.0 120.0 120.0
Max. pre-fuses
1)
[A] 16.0 16.0 25.0 40.0 50.0 60.0 80.0 125.0 150.0 150.0 150.0
Supply voltage (VDE 0160) [V] 3 x 200/220/230 ±10% 3 x 220/230/240
Supply frequency [Hz] 50/60
Power factor / cos. ϕ
1
0.9/1.0
Efficiency 0.96 at 100% load
Switching on input times/min. times/min. 2
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Weight (kg)
IP 007.4 7.4 7.4--------
IP 20 - - - 24.0 26.0 32.0 49.0 51.0 - - -
IP 218.0 8.0 8.0-----143.0 145.0 147.0
IP 54 11.0 11.0 11.0 34.0 37.0 48.0 63.0 65.0 143.0 145.0 147.0
Power loss CT [W] 60.0 100.0 130.0 270.0 425.0 399.0 615.0 935.0 760.0 910.0 1110
at max. load VT [W] 60.0 100.0 130.0 425.0 580.0 651.0 929.0 1350 950.0 1110 1290
Enclosure
VLT type 3002-04: IP 00 / IP 21 / IP 54
VLT type 3006-22: IP 20 / IP 54
VLT type 3032-52: NEMA 1 / 2, IP 21 / 54
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
Ambient temperature (to VDE 0160)
[°C] VLT 3002-3004: -10→ +40, operation at full load
2)
VLT 3006-3052: -10→ +45/40(CT/VT) at full load
2)
[°C] VLT 3002-3004: -30/25→ +65/70, in storage/transport
VLT 3006-3052: -25→ +65/70, in storage/transport
Frequency converter protection Protection against earthing and short-circuiting
Emission EN 55011, EN 55014
EMC standards
EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
(See section “EMC test results”)
Immunity IEC 1000-4-5 VDE 0160, ENV 50140, ENV 50141
+10%+10%
+10%+10%
+10%
-15%-15%
-15%-15%
-15%
1) VLT 3022: Only semi-conductor fuses; VLT 3032-3052: Bussman rapid type JJS built-in (see list)
2) In the range -10 to 0°C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com