136 MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Line 4kV/5Hz/CCC 1kV/2 2kV/12 - -
*
Motor 2kV/5Hz/CCC - - - -
Control lines 2kV/5Hz/CCC - 2kV/2 * - -
PROFIBUS option 2kV/5Hz/CCC - - - -
Signal interface < 3 m 1kV/5Hz/CCC - - - -
Enclosure - - -
8 kV AD
6 kV CD
10V/m
Basic standard Burst
IEC 1000-4-4
Surge
IEC 1000-4-5
ESD
IEC 1000-4-2
Radiated elec-
tromagn. field
IEC 1000-4-3
M
V
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Signal interface < 3 m OK - - - -
Enclosure - - - OK OK
Immunity
EMC testresults
Basic standard Burst
IEC 1000-4-4
Surge
IEC 1000-4-5
ESD
IEC 1000-4-2
Radiated elec-
tromagn. field
IEC 1000-4-3
M
V
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Brake OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Signal interface < 3 m OK - - - -
Enclosure - - - OK OK
Line 2kV/5kHz/DCN 2kV/2 4kV/12 - -
*
Motor 2kV/5kHz/CCC - - - -
Brake 2kV/5kHz/CCC - - - -
Control lines 2kV/5kHz/CCC - 2kV/2 * - -
PROFIBUS option 2kV/5kHz/CCC - - - -
Signal interface < 3 m 1kV/5kHz/CCC - - - -
Enclosure - - -
8 kV AD
6 kV CD
10V/m
VLT
®
3011-3052 380-500V, VLT
®
3006-3022 200V
VLT
®
3060-3250 380-500V, VLT
®
3032-3052 200V
Acceptance criteria according to: IEC 22G/21/CDV, EN50082-2, 175R0740
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
* Injection on cable shield
** 2,3 x Û
N
: max. testpulse 1250 V peak
Acceptance criteria according to: IEC 22G/21/CDV, EN50082-2, 175R0740
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
* Injection on cable shield
** 2,3 x Û
N
: max. testpulse 1350 V peak
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for Danfoss VLT 3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3000 Series and is the answer not in the manual?

Danfoss VLT 3000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3000 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals