EasyManuals Logo
Home>Danfoss>DC Drives>VLT 5027

Danfoss VLT 5027 User Manual

Danfoss VLT 5027
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
2. The values are stated by the motor supplier.
3. The values are obtained by means of manual
measurements:
-
R
S
can be calculated by measuring
the resistance R
PHASE-to-PHASE
be-
tween two phase terminals. If
R
PHASE-to-PHASE
is lower than 1-2
ohm (typically motors >4-5.5 kW,
400 V), a special ohm-meter should
be used (Thomson bridge or simi-
lar). R
S
= 0.5 x R
PHASE-to-PHASE
4. The factory settings of R
S
, selected by the
adjustable frequency drive itself on the basis
of the motor nameplate data, are used.
NOTE
If the setting in parameter 102-109 is
changed, the parameters 110-118 will re-
turn to factory setting. If using special mo-
tor characteristics a change in parameter
102-109 affects parameter 422.
109 Stator reactance
(STATOR REACT.)
Value:
depends on the choice of motor
Function:
After setting motor data in parameters 102-106, a
number of adjustments of various parameters are
made automatically, including the stator reactance
X
S
. The shaft performance can be improved by fine-
tuning R
S
and X
S
, see procedure below.
Description of choice:
X
S
can be set as follows:
1. Automatic motor adaptation, where the ad-
justable frequency drive measures on the
motor to determine the value. All compensa-
tions are reset to 100%.
2. The values are stated by the motor supplier.
3. These values are obtained by means of man-
ual measurements:
- X
S
can be calculated by connect-
ing a motor to line power and meas-
uring the phase-to-phase voltage
U
L
as well as the idling current I
Ɏ
.
Alternatively, these values can be
recorded during operation in idle
running state at the rated motor fre-
quency f
M,N
, slip compensation (par.
115) = 0% and load compensation
at high speed (par. 114) = 100%.
X
S
=
U
L
l
ˎ
4. The factory settings of X
S
, selected by the
adjustable frequency drive itself on the basis
of the motor nameplate data, are used.
NOTE
If the setting in parameter 102-109 is
changed, the parameters 110-118 will re-
turn to the factory setting. If using special
motor characteristics, a change in param-
eter 102-109 affects parameter 422.
110 Motor magnetizing, 0 rpm
(MOT. MAGNETIZING)
Value:
0 - 300 %
100 %
Function:
This parameter can be used if a different thermal load
on the motor is desired when running at low speed.
This parameter is used in connection with parameter
111.
Description of choice:
Enter a value stated as a percentage of the rated mag-
netizing current.
Too low setting may lead to a reduced torque on the
motor shaft.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
92 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals