Control panel (LCP)
The front of the adjustable frequency drive features a
control panel - LCP (Local Control Panel), which
makes up a complete interface for operation and mon-
itoring of the VLT 5000 Series.
The control panel is detachable and can - as an alter-
native - be installed up to 3 meters away from the
adjustable frequency drive, e.g. on a front panel, by
means of a mounting kit option.
The functions of the control panel can be divided into
three groups:
•display
keys for changing program parameters
keys for local operation
All data are indicated by means of a 4-line alpha-nu-
meric display, which in normal operation is able to
show 4 measurements and 3 operating conditions
continuously. During programming, all the information
required for quick, effective parameter Setup of the
adjustable frequency drive will be displayed. As a sup-
plement to the display, there are three LEDs for volt-
age (power or 24 V external), warning and alarm.
All program parameters of the adjustable frequency
drive can be changed immediately from the control
panel, unless this function has been blocked via pa-
rameter 018.
Control panel - display
The LCD-display has rear lighting and a total of 4 al-
pha-numeric lines together with a box that shows the
direction of rotation (arrow) and the chosen Setup as
well as the Setup in which programming is taking place
if that is the case.
12345678
SETUP
1
12345678901234567890
12345678901234567890
12345678901234567890
175ZA443.10
1st line
2nd line
3rd line
4th line
1st line shows up to 3 measurements continuously in
normal operating status or a text which explains the 2
nd line.
2nd line shows a measurement with related unit con-
tinuously, regardless of status (except in the case of
alarm/warning).
3rd line is normally blank and is used in the menu
mode to show the selected parameter number or pa-
rameter group number and name.
4th line is used in operating status for showing a status
text or in data change mode for showing the mode or
value of the selected parameter.
An arrow indicates the direction of rotation of the mo-
tor. Furthermore, the Setup which has been selected
as the Active Setup in parameter 004 is shown. When
programming another Setup than the Active Setup, the
number of the Setup which is being programmed will
appear to the right. This second Setup number will
flash.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 71
Operation of the VLT

Table of Contents

Other manuals for Danfoss VLT 5032

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5032 and is the answer not in the manual?

Danfoss VLT 5032 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5032
CategoryDC Drives
LanguageEnglish

Related product manuals