The Menu mode makes it possible to select
and change all parameters at the user's op-
tion. However, some parameters will be
"missing", depending on the choice of con-
figuration (parameter 100), e.g. open loop
hides all the P.I.D. parameters.
Quick Setup
The Quick Setup starts with pressing the [QUICK
MENU] key, which brings out the following read-out on
the display:
50.0 HZ
001 LANGUAGE
ENGLISH
QUICK MENU 1 OF 13
At the bottom of the display, the parameter number
and name are given together with the status/value of
the first parameter under Quick Setup. The first time
the [Quick Menu] key is pressed after the unit has been
switched on, the read-outs always start at pos. 1 - see
table below.
Parameter selection
The selection of parameter is effected by means of the
[+/-] keys. The following parameters are accessible:
Pos.: No.: Parameter: Unit:
1 001 Language
2 102 Motor output [kW]]
3 103 Motor voltage [V]
4 104 Motor frequency [Hz]
5 105 Motor current [A]
6 106 Rated motor speed [rpm]
7 107 Automatic motor adaptation,
AMA
8 204 Minimum reference [Hz]
9 205 Maximum reference [Hz]
10 207 Ramp-up time 1 [sec.]
11 208 Ramp-down time 1 [sec.]
12 002 Local/remote control
13 003 Local reference
Menu mode
The Menu mode is started by pressing the [MENU]
key, which produces the following read-out on the dis-
play:
50.0 Hz
FREQUENCY
0 KEYB.&DISPLAY
Line 3 on the display shows the parameter group num-
ber and name.
Parameter selection
In the Menu mode the parameters are divided into
groups. Selection of parameter group is effected by
means of the [<>] keys.
The following parameter groups are accessible:
Group no. Parameter group:
0 Operation & Display
1 Load & Motor
2 References & Limits
3 Inputs & Outputs
4 Special functions
5 Serial communication
6 Technical functions
7 Application Options
8 Fieldbus Profile
9 Fieldbus Communication
When the desired parameter group has been selected,
each parameter can be chosen by means of the [+/-]
keys:
FREQUENCY
001 LANGUAGE
ENGLISH
50.0 Hz
The 3rd line of the display shows the parameter num-
ber and name, while the status/value of the selected
parameter are shown in line 4.
Changing data
Regardless of whether a parameter has been selected
under the Quick menu or the Menu mode, the proce-
dure for changing data is the same.
Pressing the [CHANGE DATA] key gives access to
changing the selected parameter, following which the
underlining in line 4 will flash on the display.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 75
Operation of the VLT

Table of Contents

Other manuals for Danfoss VLT 5032

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5032 and is the answer not in the manual?

Danfoss VLT 5032 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5032
CategoryDC Drives
LanguageEnglish

Related product manuals