1-20 Motor Power [kW]
Range: Function:
Application
dependent*
[Application dependant] Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. This parameter is visible in LCP if
par. 0-03
Regional Settings
is
International
[0].
NB!
Four sizes down, one size up from nominal unit rating.
1-22 Motor Voltage
Range: Function:
400. V* [10. - 1000. V]
1-23 Motor Frequency
Range: Function:
Application
dependent*
[20 - 1000 Hz] Min - Max motor frequency: 20 - 1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to adapt the load independent settings in par. 1-50
Motor
Magnetisation at Zero Speed
to par. 1-53
Model Shift Frequency
. For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High Limit
[RPM]
and par. 3-03
Maximum Reference
to the 87 Hz application.
1-24 Motor Current
Range: Function:
7.20 A* [0.10 - 10000.00 A]
NB!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range: Function:
1420. RPM* [100 - 60000 RPM] Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
NB!
This parameter cannot be adjusted while the motor is running.
5-12 Terminal 27 Digital Input
Option: Function:
Select the function from the available digital input range.
No operation [0]
Reset [1]
Coast inverse [2]
Coast and reset inverse [3]
Quick stop inverse [4]
DC-brake inverse [5]
Stop inverse [6]
Start [8]
4 How to Programme
VLT
®
AutomationDrive FC 300 Operating
Instructions
46
MG.33.AG.02 - VLT
®
is a registered Danfoss trademark
4