6-92 Terminal 42 Digital Output
Option: Function:
[16] Below frequency, low
[17] Above frequency, high
[18] Out of feedb. range
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[22] Ready, no thermal warning
[23] Remote,ready,no TW
[24] Ready, no over-/ under voltage
[25] Reverse
[26] Bus OK
[27] Torque limit & stop
[28] Brake, no brake warning
[29] Brake ready, no fault
[30] Brake fault (IGBT)
[31] Relay 123
[32] Mech brake ctrl
[36] Control word bit 11
[37] Control word bit 12
[40] Out of ref range
[41] Below reference, low
[42] Above ref, high
[45] Bus ctrl.
[46] Bus control, timeout: On
[47] Bus control, timeout: Off
[56] Heat sink cleaning warning, high
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic rule 0
[71] Logic rule 1
[72] Logic rule 2
[73] Logic rule 3
[74] Logic rule 4
[75] Logic rule 5
[80] SL digital output A
[81] SL digital output B
[82] SL digital output C
[83] SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref active
[166] Remote ref active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[170] Homing Completed
[171] Target Position Reached
[172] Position Control Fault
6-92 Terminal 42 Digital Output
Option: Function:
[173] Position Mech Brake
[174] TLD indicator
[175] Running on tension
[176] Ready to run
[177] End of roll
[193] Sleep Mode
[194] Broken Belt Function
[198] Drive Bypass
4.7.2 Positioning Control Settings
37-01 Pos. Feedback Source
Option: Function:
[1] * MCB102
[2] MCB103
37-02 Pos. Target
Range: Function:
0* [-1073741824 - 1073741824 ]
37-03 Pos. Type
Option: Function:
[0] * Absolute
[1] Relative
37-04 Pos. Velocity
Range: Function:
100 RPM* [1 - 30000 RPM]
37-05 Pos. Ramp Up Time
Range: Function:
5000 ms* [50 - 100000 ms]
37-06 Pos. Ramp Down Time
Range: Function:
5000 ms* [50 - 100000 ms]
37-07 Pos. Auto Brake Ctrl
Option: Function:
[0] Disable
[1] * Enable
37-08 Pos. Hold Delay
Range: Function:
0 ms* [0 - 10000 ms]
37-09 Pos. Coast Delay
Range: Function:
200 ms* [0 - 1000 ms]
37-10 Pos. Brake Delay
Range: Function:
200 ms* [0 - 1000 ms]
Positioning Control
VLT
®
AutomationDrive FC 360
24 Danfoss A/S © 11/2014 All rights reserved. MG06E102
44

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals