Parameter 5-53 Term. 29 High Ref./Feedb. Value
Table 367: Parameter 5-53 Term. 29 High Ref./Feedb. Value
5-53 Term. 29 High Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 Reference- Feed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see also parameter 5-58 Term. 33 High
Ref./Feedb. Value. Select terminal 29 as a digital input (parameter 5-02 Terminal 29 Mode = [0] Input (default) and parameter 5-13 Ter-
minal 29 Digital Input = applicable value).
Parameter 5-54 Pulse Filter Time Constant #29
Table 368: Parameter 5-54 Pulse Filter Time Constant #29
5-54 Pulse Filter Time Constant #29
Default value: 100 ms
Parameter type: Range, 1 - 1000 ms
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: False
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal. If there is much noise in the system
this is an advantage. A high time constant value results in better dampening but also increases the time delay through the filter.
Parameter 5-55 Term. 33 Low Frequency
Table 369: Parameter 5-55 Term. 33 Low Frequency
5-55 Term. 33 Low Frequency
Default value: 100 Hz
Parameter type: Range, 0 - 110000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Enter the low frequency corresponding to the low motor shaft speed (that is low reference value) in parameter 5-57 Term. 33 Low
Ref./Feedb. Value.
Parameter 5-56 Term. 33 High Frequency
Table 370: Parameter 5-56 Term. 33 High Frequency
5-56 Term. 33 High Frequency
Default value: Size related
Parameter type: Range, 0 - 110000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Enter the high frequency corresponding to the high motor shaft speed (that is high reference value) in parameter 5-58 Term. 33 High
Ref./Feedb. Value.
Parameter 5-57 Term. 33 Low Ref./Feedb. Value
Table 371: Parameter 5-57 Term. 33 Low Ref./Feedb. Value
5-57 Term. 33 Low Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the low reference value [RPM] for the motor shaft speed. This is also the low feedback value, see also parameter 5-52 Term. 29
Low Ref./Feedb. Value.
AU275636650261en-000101 / 130R0334 | 219Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals