Illustration 65: Pulse Input
Parameter 5-50 Term. 29 Low Frequency
Table 364: Parameter 5-50 Term. 29 Low Frequency
5-50 Term. 29 Low Frequency
Parameter type: Range, 0 – 110000 Hz
Change during operation: True
Enter the low frequency limit corresponding to the low motor shaft speed (that is low reference value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to
Illustration 65.
Parameter 5-51 Term. 29 High Frequency
Table 365: Parameter 5-51 Term. 29 High Frequency
5-51 Term. 29 High Frequency
Default value: Size related
Parameter type: Range, 0 – 110000 Hz
Change during operation: True
Enter the high frequency limit corresponding to the high motor shaft speed (that is high reference value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
Parameter 5-52 Term. 29 Low Ref./Feedb. Value
Table 366: Parameter 5-52 Term. 29 Low Ref./Feedb. Value
5-52 Term. 29 Low Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 Reference- Feed-
backUnit
Change during operation: True
Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback value, see also parameter 5-57
Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (parameter 5-02 Terminal 29 Mode = [0] Input (default) and parameter
5-13 Terminal 29 Digital Input = applicable value).