FC 102
N500
N560
N630
N710
N800
Intermittent (60 s overload) (at 550 V) [A]
575
656
693
839
978
Continuous (at 575/690 V) [A]
500
570
630
730
850
Intermittent (60 s overload) (at 575/690
V) [A]
550
627
693
803
935
Continuous kVA (at 550 V) [kVA]
498
568
600
727
847
Continuous kVA (at 575 V) [kVA]
498
568
627
727
847
Continuous kVA (at 690 V) [kVA]
598
681
753
872
1016
Maximum input current
Continuous (at 525 V) [A]
504
574
607
735
857
Continuous (at 575/690 V) [A]
482
549
607
704
819
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with disconnect [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with contactor [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Motor [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
Drive module power loss at 600 V [W]
(1)(2)
(3)
6879
8076
9208
10346
12723
Drive module power loss at 690 V [W]
(1)(2)
(3)
6715
7852
8921
10066
12321
Drive eciency
(2)
0.98
0.98
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–500
0–500
0–500
0–500
0–500
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C
(°F)]
80 (176)
80 (176)
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
dU/dt lter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
AQ357954340588en-000201 / 130R0881146 | Danfoss A/S © 2020.09
Specications
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N500 and is the answer not in the manual?

Danfoss VLT FC 102 N500 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N500
CategoryDC Drives
LanguageEnglish

Related product manuals