FC 102
N500
N560
N630
N710
N800
Sine-wave lter overtemperature trip [°C
(°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor eciency (IE/IE3 border line). Lower ecienc y motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-eciency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy eciency
class, see the Ambient Conditions section. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
3
See also Input Power Option Losses section.
4
If using an output lter, the output frequency is limited further. See the Motor Output (U, V, W) section.
10.2 Mains Supply
The unit is suitable for use on a circuit capable of delivering not more than 65 kA short circuit current rating (SCCR) at 480/600 V.
Supply terminals
L1, L2, L3
Supply voltage
(1)
380–480/500 V ±10%, 525–690 V ±10%
Supply frequency
50/60 Hz ±5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
(2)
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos Φ)
Near unity (>0.98)
Switching on the input supply L1, L2, and L3 (power-ups)
Maximum 1 time/2 minutes
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1
Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expec-
ted at mains voltage lower than 10% below the drive's lowest rated supply voltage.
2
Calculations based on UL/IEC 61800-3.
10.3 Motor Output and Motor Data
10.3.1 Motor Output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency (without sine-wave lter)
0–590 Hz
(1)
Output frequency (with sine-wave lter and no derating)
0–60 Hz without derating
Output frequency (with sine-wave lter and derating)
0–100 Hz
Output frequency in ux mode
0–300 Hz
Switching on output
Unlimited
Ramp times
0.01–3600 s
1
Dependent on voltage and power.
10.3.2 Torque Characteristics
Starting torque (constant torque)
Maximum 150% for 60 s once in 10 minutes
(1)
Starting/overload torque (variable torque)
Maximum 110% up to 0.5 s once in 10 minutes
(1)
Torque rise time in ux (for 5 kHz f
sw
)
1 ms
AQ357954340588en-000201 / 130R0881 | 147Danfoss A/S © 2020.09
Specications
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N500 and is the answer not in the manual?

Danfoss VLT FC 102 N500 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N500
CategoryDC Drives
LanguageEnglish

Related product manuals