1.
2.
3.
4.
5.
-
-
6.
-
Procedure
Strip a section of the outer cable insulation.
Fasten a connector/cable lug to the end of the stripped cable.
Create an electrical connection between the cable shield and ground by securing the stripped wire under the cable clamp.
Connect the ground cable to the nearest grounding terminal in accordance with the grounding instructions provided in
5.8.6 Connecting to Ground.
Connect the 3-phase AC motor cable to the sine-wave terminals U, V, and W.
If the enclosed drive has 1 sine-wave lter cabinet, run 1 set of motor cables to the cabinet.
If the enclosed drive has 2 sine-wave lter cabinets, run 2 sets of motor cables, 1 set to each sine-wave lter cabinet.
N O T I C E
Each sine-wave cabinet must have the same number of motor phase cables and they must be in quantities of 2
(for example, 2, 4, 6, or 8). 1 cable is not allowed. The cables are required to be equal length.
Tighten the terminals in accordance with the specications shown in 10.11 Fastener Torque Ratings.
AQ357954340588en-000201 / 130R088186 | Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide