Table 48: Fastener Torque Ratings
Location Bolt size Torque [Nm (in-lb)]
Mains terminals M10/M12 19 (168)/37 (335)
Motor terminals M10/M12 19 (168)/37 (335)
Ground terminals M8/M10 9.6 (84)/19.1 (169)
Brake terminals M8 9.6 (84)
Load sharing terminals M10/M12 19 (168)/37 (335)
Regen terminals (Enclosures E1h/E2h) M8 9.6 (84)
Regen terminals (Enclosures E3h/E4h) M10/M12 19 (168)/37 (335)
Relay terminals 0.5 (4)
Door/panel cover M5 2.3 (20)
Cable entry plate M5 2.3 (20)
Heat sink access panel M5 2.3 (20)
Serial communication cover M5 2.3 (20)