8.5 Troubleshooting
Table 41: Troubleshooting
Symptom Possible cause Test Solution
Display dark/No
function
Missing input power. Check for loose connections. Check the input power source.
Missing or open fuses. See Open power fuses in this table
for possible causes.
Follow the recommendations provided.
No power to the LCP. Check the LCP cable for proper
connection or damage.
Replace the faulty LCP or connection
cable.
Short circuit on control volt-
age (terminal 12 or 50) or at
control terminals.
Check the 24 V control voltage
supply for terminal 12/13 to 20–39,
or 10 V supply for terminals 50–55.
Wire the terminals properly.
Incompatible LCP (LCP from
VLT
®
2800 or 5000/6000/8000/
FCD or FCM).
Use only LCP 101 (P/N 130B1124) or
LCP 102 (P/N. 130B1107).
Wrong contrast setting. To adjust the contrast, press [Status] +
[]/[].
Display (LCP) is defective. Test using a different LCP. Replace the faulty LCP or connection
cable.
Internal voltage supply fault
or SMPS is defective.
Contact supplier.
Intermittent dis-
play
Overloaded supply (SMPS)
due to improper control wir-
ing or a fault within the AC
drive.
To rule out a problem in the con-
trol wiring, disconnect all control
wiring by removing the terminal
blocks.
If the display stays lit, the problem is in
the control wiring. Check the wiring for
shorts or incorrect connections. If the
display continues to cut out, follow the
procedure for Display dark\No function.
Motor not run-
ning
Service switch open or miss-
ing motor connection.
Connect the motor and check the serv-
ice switch.
No mains power with 24 V DC
option card.
Apply mains power.
LCP stop. Depending on the operating mode,
press [Auto On] or [Hand On].
Missing start signal (Standby). Apply a valid start signal.
Motor coast signal active
(Coasting).
Apply 24 V on terminal 27 or program
this terminal to [0] No operation.
Wrong reference signal
source.
Check reference signal:
Local
Remote or bus reference?
Preset reference active?
Terminal connection correct?
Scaling of terminals correct?
Reference signal available?
Program correct settings. Check param-
eter 3-13 Reference Site. Set preset refer-
ence active in parameter group 3-1* Ref-
erences. Check for correct wiring. Check
scaling of terminals. Check reference
signal.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707
124 | Danfoss A/S © 2020.01

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals