Example:
e30bg283.10
10 mm (0.4)
12 13 18 19 27 29 32 33
Illustration 35: Connecting a Solid Control Cable to the Terminal Box
Illustration 36: Connecting a Flexible Control Cable to the Terminal Box
5.11.6 Disconnecting the Control Cable from the Control Terminals
Procedure
1. To open the contact, insert a small screwdriver into the slot between the terminal holes and push the screwdriver inward.
2. Pull gently on the wire to free it from the control terminal contact.
5.11.7 Enabling Motor Operation
Context:
If the status line at the bottom of the LCP reads AUTO REMOTE COAST, the unit is ready to operate, but is missing an input signal on
terminal 27. Digital input terminal 27 is designed to receive a 24 V DC external interlock command that allows the drive to operate
when using factory default programming values.
Electrical Installation
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707
60 | Danfoss A/S © 2020.01