NOTICE
SOFTWARE DOWNLOAD
For commissioning via a PC, install VLT
®
Motion Control Tool MCT 10 set-up software. A basic version, which is sufficient for
most applications, is available for download. An advanced version, which can commission multiple drives at once, can be
ordered.
-
See https://www.danfoss.com/en/service-and-support/downloads/?sort=title_asc&filter=download-type%3Dtools.
Procedure
1. Press [Main Menu] on the LCP.
2. Select 0–** Operation/Display and press [OK].
3. Select 0–0* Basic Settings and press [OK].
4. Select parameter 0-03 Regional Settings and press [OK].
5. Select [0] International or [1] North America as appropriate and press [OK]. (This action changes the default settings for some basic
parameters).
6. Press [Quick Menus] on the LCP and then select 02 Quick Setup.
7. If needed, change the following parameter settings. Motor data is found on the motor nameplate.
A Parameter 0-01 Language (English)
B Parameter 1-20 Motor Power [kW] (4.00 kW)
C Parameter 1-22 Motor Voltage (400 V)
D Parameter 1-23 Motor Frequency (50 Hz)
E Parameter 1-24 Motor Current (9.00 A)
F Parameter 1-25 Motor Nominal Speed (1420 RPM)
G Parameter 5-12 Terminal 27 Digital Input (Coast Inverse)
H Parameter 3-02 Minimum Reference (0.000 RPM)
I Parameter 3-03 Maximum Reference (1500.000 RPM)
J Parameter 3-41 Ramp 1 Ramp up Time (3.00 s)
K Parameter 3-42 Ramp 1 Ramp Down Time (3.00 s)
L Parameter 3-13 Reference Site (Linked to Hand/Auto)
M Parameter 1-29 Automatic Motor Adaptation (AMA) (Off)
6.3.4 Configuring Automatic Energy Optimization
Context:
Automatic energy optimization (AEO) is a procedure that minimizes voltage to the motor, reducing energy consumption, heat, and
noise.
Procedure
1. Press [Main Menu].
2. Select 1–** Load and Motor and press [OK].
3. Select 1–0* General Settings and press [OK].
4. Select parameter 1-03 Torque Characteristics and press [OK].
5. Select either [2] Auto Energy Optim CT or [3] Auto Energy Optim VT and press [OK].
Starting the Drive
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707
68 | Danfoss A/S © 2020.01

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals