Parameter International default parameter
value
North American default parameter
value
Parameter 1-21 Motor Powr [HP]
(2)
– –
Parameter 1-22 Motor Voltage [V] 230/400/575 208/460/575
Parameter 1-23 Motor Frequency 50 Hz 60 Hz
Parameter 3-03 Maximum Reference 50 Hz 60 Hz
Parameter 3-04 Reference Function Sum External/Preset
Parameter 4-13 Motor Speed High Limit
(3)
1500 RPM 1800 RPM
Parameter 4-14 Motor Speed High Limit [Hz]
(4)
50 Hz 60 Hz
Parameter 4-19 Max Output Frequency 100 Hz 120 Hz
Parameter 4-53 Warning Speed High 1500 RPM 1800 RPM
Parameter 5-12 Terminal 27 Digital Input Coast inverse External interlock
Parameter 5-40 Function Relay Alarm No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb. Value 50 Hz 60 Hz
Parameter 6-50 Terminal 42 Output Speed 0-HighLim Speed 4–20 mA
Parameter 14-20 Reset Mode Manual reset Infinite auto reset
Parameter 22-85 Speed at Design Point (RPM) 1500 RPM 1800 RPM
Parameter 22-86 Speed at Design Point (Hz) 50 Hz 60 Hz
Parameter 24-04 Fire Mode Max Reference 50 Hz 60 Hz
1
Visible only when parameter 0-03 Regional Settings is set to [0] International.
2
Visible only when parameter 0-03 Regional Settings is set to [1] North America.
3
Visible only when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4
Visible only when parameter 0-02 Motor Speed Unit is set to [1] RPM.
Appendix
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707| 161
Danfoss A/S © 2020.01