VLT
®
FCD Series
■ Technical data, mains supply 3 x 380 - 480 V
According to international
standards
Type 303 305 307 311 315 322 330 335**
Output current I
INV.
[A] 1.4 1.8 2.2 3.0 3.7 5.2 7.0 7.6
(3 x 380-480V) I
MAX
(60s) [A] 2.2 2.9 3.5 4.8 5.9 8.3 11.2 11.4
Output power (400
V)
S
INV.
[KVA] 1.0 1.2 1.5 2.0 2.6 3.6 4.8 5.3
Typical shaft output P
M,N
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.0 3.3
Typical shaft output P
M,N
[HP] 0.50 0.75 1.0 1.5 2.0 3.0 4.0 5*
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10
Input current I
L,N
[A] 1.2 1.6 1.9 2.6 3.2 4.7 6.1 6.8
(3 x 380-480 V) I
L,MAX
(60s)[A] 1.9 2.6 3.0 4.2 5.1 7.5 9.8 10.2
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses [IEC]/UL
2)
[A] 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25
Efficiency
3)
[%] 96
Power loss at max.
load
[W] 22 29 40 59 80 117 160 190
Weight [kg] 5.8 5.8 5.8 5.8 5.8 9.5 9.5 9.5
* At mains voltage min 3 x 460 - 480 V
** t
amb
max. 35° C.
1. American Wire Gauge. Max. cable cross
section is the largest cable cross section that can
be attached to the terminals. Always observe
national and local regulations.
2. Typr gG / gL pre fuses or corrosponding
circuit brakers should be used.
IfyouwanttomaintainUL/cULbranchcircuitfuses
according to NEC should be used. Alternatively
a circuit braker Danfoss type CTI 25 MB or
equivalent should be used.
To be placed for protection in a circuit that is
capable of supplying a maximum of 100,000 amps
for fuses / 10,000 amps for circuit brakers.
3. Measured using a 10 m screened/armoured
motor cable with a rated load and rated frequency.
MG.04.B7.02 - VLT is a registered Danfoss trademark
116