In the factory the process regulator is preset with
an active anti windup function. This function means
that when either a frequency limit, a current limit or
a voltage limit is reached, the integrator is initialised
at a frequency corresponding to the present output
frequency. This is a means of avoiding the integration
of a variance between the reference and the processs
actual mode that cannot be deregulated by means of
a change of speed. This function can be deselected
in parameter 438 Process PID anti windup.
S
tarting conditions
In some applications the optimal setting of the
process regulator will mean that a relatively long
period of time will pass before the required process
condition is achieved. In these applications it can
be a good idea to define an output frequency to
which the frequency converter must run the motor
before the process regulator is activated. This is
done by programming a start frequency in parameter
439 Process PID start frequency.
Handling of feedback
Feedback handling is depicted in this flowchart.
The flowchart shows which parameters can affect the
handling of feedback and how. A choice can be made
between voltage, current and pulse feedback signals.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
70

Table of Contents

Other manuals for Danfoss VLT FCD 315

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 315 and is the answer not in the manual?

Danfoss VLT FCD 315 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 315
CategoryDC Drives
LanguageEnglish

Related product manuals