VLT
®
FCD Series
Programming, FCD
300
Logic or [3]
Dig. input Ser. port Function
0 0 Coasting
0 1 Coasting
1 0 Coasting
1 1 Motor running
503 Quick-stop
(Q STOP SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is running
and when it is in Quick-stop mode, when each of
the following is selected: Digital input [0], Serial
port [1], Logic and [2] or Logic or [3].
NB!:
Note that Quick-stop inverse and Bit 04 in
the control word are active at logic 0.
Digital input [0]
Dig. input Serial port Function
0 0 Quick-stop
0 1 Quick-stop
1 0 Motor running
1 1 Motor running
Serial port [1]
Dig. input Serial port Function
0 0 Quick-stop
0 1 Motor running
1 0 Quick-stop
1 1 Motor running
Logic and [2]
Dig. input Serial port Function
0 0 Quick-stop
0 1 Motor running
1 0 Motor running
1 1 Motor running
Logic or [3]
Dig. input Serial port Function
0 0 Quick-stop
0 1 Quick-stop
1 0 Quick-stop
1 1 Motor running
504 DC brake
(DC BRAKE SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is
running and the DC braking when each of the
following is selected Digital input [0], Serial port
[1], Logic and [2] or Logic or [3].
NB!:
Note that DC braking i nverse and Bit 02
in
the control word are active at logic 0.
Digital input [0]
Dig. input Ser. port Function
0 0 DC braking
0 1 DC braking
1 0 Motor running
1 1 Motor running
Serial port [1]
Dig. input Ser. port Function
0 0 DC braking
0 1 Motor running
1 0 DC braking
1 1 Motor running
Logic and [2]
Dig. input Ser. port Function
0 0 DC braking
0 1 Motor running
1 0 Motor running
1 1 Motor running
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
89

Table of Contents

Other manuals for Danfoss VLT FCD 315

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 315 and is the answer not in the manual?

Danfoss VLT FCD 315 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 315
CategoryDC Drives
LanguageEnglish

Related product manuals