Tightening Torques
Cover (lid) screws: 19.5 - 21.2 lb-in (2.2 - 2.4 Nm)
Plastic cable entrance plugs: 19.5 lb-in (2.2 Nm)
L1, L2, L3 (AC Line) screws (FCM 305-340): 5 - 7 lb-in (0.5 - 0.6 Nm)
L1, L2, L3 (AC Line) screws (FCM 355-375): 15 lb-in (1.2 - 1.5 Nm)
Earth Ground: 30.1 lb-in (3.4 Nm)
Terminal screws require a max 2.5 mm
flat-blade screwdriver.
AC Line screws require a 8mm flat-blade screwdriver.
Earth ground and cable clamp screws all require
T-20 Torx or flat-blade screwdriver.
Lid screws require Philips screwdriver.
Maximum Cable Cross Section
Note:
Us60Ccopperwireorbetter
AWG mm
2
Max size AC Line cable (FCM 305-340): 10 4.0
Max size AC Line cable (FCM 355-375): 6 10
Max size control cable: 16 1.5
Max size serial communication cable: 16 1.5
Earth Ground: 6 10
Screw Sizes
Cover (lid) screws: M5
Earth Ground and Cable Clamp screws (FCM 305-340): M4
Earth Ground and Cable Clamp screws (FCM 355-375): M5
MG.03.H3.02 - VLT is a registered Danfoss trademark
14

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCM 315 and is the answer not in the manual?

Danfoss VLT FCM 315 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCM 315
CategoryDC Drives
LanguageEnglish

Related product manuals