EasyManuals Logo
Home>Danfoss>DC Drives>VLT FCM Series

Danfoss VLT FCM Series User Manual

Danfoss VLT FCM Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
VLT
®
FCM Series
PC Software tools
PC Software - MCT 10
All drives are equipped with a serial communication
port. We provide a PC tool for communication
between PC and frequency converter, VLT Motion
Control Tool MCT 10 Set-up Software.
MCT 10 Set-up Software
MCT 10 has been designed as an easy to use interactive
tool for setting parameters in our frequency converters.
The MCT 10 Set-up Software will be useful for:
Planning a communication network off-line. MCT 10
contains a complete frequency converter database
Commissioning frequency converters on line
Saving settings for all frequency converters
Replacing a drive in a network
Expanding an existing network
Future developed drives will be supported
The MCT 10 Set-up Software Modules
The following modules are included in the
software package:
MCT 10 Set-up Software
Setting parameters
Copy to and from frequency
converters
Documentation and print out of
parameter settings incl. diagrams
SyncPos
Creating SyncPos programme
Ordering number:
Please order your CD containing MCT 10 Set-up
Software using code number 130B1000.
PC Software - VLT Software Dialog:
For single or few unit installations a basic software
package, VLT Software Dialog, is available. Please
order using code number 175Z0967.
Serial bus
Telegram communication
C
ontrol and reply telegrams
The telegram communication in a master/slave
system is controlled by the master. A maximum
of 31 slaves (FC motors) can be connected to one
master, unless a repeater is used - see also the
description of the address format.
The master continuously sends control telegrams
addressed to the slaves and awaits reply
telegrams from these. The response time of
the slaves is maximum 50 ms.
Only a slave that has received a faultless telegram
addressed to that slave will respond by sending
back the telegram unchanged.
B
roadcast
A master can send the same telegram at the same
time to all slaves connected to the bus. In such
broadcast communication, the control telegram
broadcast bit of the address bit has a value of 1 (see
VLT address). Address bits 0-4 are not used.
C
ontents of a byte
Each transmitted sign begins with a start bit.
Subsequently, 8 databits are transmitted. Each sign
is given via a parity bit set at "1" when there is an
even parity (i.e. an even number of binary 1sinthe8
databits and parity bits together). The sign ends with a
stop bit and thus consists of a total of 11 bits.
Telegram build-up
Each telegram begins with a startbyte (STX) = 02 Hex,
followed by a byte that gives the telegram length (LGE)
MG.03.H3.02 - VLT is a registered Danfoss trademark
78

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCM Series and is the answer not in the manual?

Danfoss VLT FCM Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCM Series
CategoryDC Drives
LanguageEnglish

Related product manuals