Turn off the FC motor and check whether the
motor shaft can be turned.
NB!:
If shock loads occur this alarm may appear.
ALARM: 14
Earth fault (EARTH FAULT):
There is a discharge from the output phases
to earth, either between the inverter and the
motororinthemotoritself.
ALARM: 15
Supply fault (SWITCH MODE FAULT):
Fault in the switch mode power supply (internal
24 V supply).
Contact your Danfoss supplier.
ALARM: 16
Short-circuiting (CURR.SHORT CIRCUIT):
There is short-circuiting on the motor terminals
or the motor itself.
Contact your Danfoss supplier.
ALARM: 17
Standard bus timeout (STD BUSTIMEOUT)
There is no communication to the FC motor. The
warning will only be active when parameter 514 has
been set to another value than OFF.
If parameter 514 has been set to stop and trip,
it will first give a warning and then ramp down
until it trips, while giving an alarm.
Parameter 513 Bus time interval could possibly
be increased.
WARNING/ALARM 18
HPFB bus timeout (HPFB BUS TIMEOUT)
There is no communication with the FC motor. The
warning will only be active when parameter 804 has
been set to another value than OFF. If parameter 804
has been set to Stop and trip, it will first give a warning
and then ramp down until it trips, while giving an alarm.
Parameter 803 Bus time out could possibly
be increased.
WARNING 33
Out of frequency range:
This warning is active if the output frequency has
reached parameter 201 Output frequency low limit or
parameter 202 Output frequency high limit.
WARNING/ALARM 34
HPFB error (HPFB ALARM):
The profibus communication is not working correctly.
ALARM 35
Inrush fault (INRUSH FAULT):
This warning occurs when the unit has been switched
on too many times within 1 minute.
WARNING/ALARM 36
Overtemperature (OVERTEMPERATURE):
ALARM: 37
Internal error (INTERNAL ERROR):
An error has occurred in the system. Contact
your Danfoss supplier.
Warning word, extended Status word and
Alarm word
Warning word, extened status word and alarm
wordare shown on the display in Hex format. If
there are more than one warning or alarm, a sum
of all warnings or alarms will be shown.
Warning word, extened status word and alarm
word can also be displayed using the serial bus
in parameter 540, 541 and 538.
Bit (Hex) Warning word (P. 540)
00000008 HPFB timeout
00000010 Standard bus timeout
00000040 Current limit
00000200 Inverter overload
00001000 Voltage warning low
00002000 Voltage warning high
00004000 Phase loss
00010000 Live zero error warning
00400000 Output freq. limit warning
00800000 HPFB error
40000000 24 V supply warning
80000000 Inverter temp. high
Bit (Hex) Extended status word (P.541)
01 Ramping
04 Start clockwise/counterclockwise
08 Slow down
10 Catch-up
8000 Frequency limit
MG.03.H3.02 - VLT is a registered Danfoss trademark
96

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCM Series and is the answer not in the manual?

Danfoss VLT FCM Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCM Series
CategoryDC Drives
LanguageEnglish

Related product manuals