VLT
®
FCM Series
Bit 09, Local operation / bus control:
Bit 09 = "0" means that [STOP/RESET] is activated
on the control unit, or that Local control in parameter
002 Local/remote operation is selected. It is not
possible to control the frequency converter via
serial communication. Bit 09 = "1" means that
it is possible to control the frequency converter
via serial communication.
B
it 10, Out of range/frequency:
Bit 10 = "0", if the output frequency has reached
the value in parameter 201 Output frequency
low limit or parameter 202 Output frequency
high limit. Bit 10 = "1" means that the output
frequency is within the defined limits.
B
it 11, Not running / running:
Bit 11 = "0" means that the motor is not running. Bit
11 = "1" means that the FC motor has a start signal or
that the output frequency is greater than 0 Hz.
B
it 13, Voltage OK / above limit:
Bit 13 = "0" means that the voltage limits of the
FC motor have not been exceeded. Bit 13 =
"1" means that the DC voltage of the FC motor
intermediate circuit is too low or too high.
B
it 14, Current OK / above limit:
Bit 14 = "0" means that the motor current is
lower than the torque limit selected in parameter
221. Bit 14 = "1" means that the torque limit in
parameter 221 has been exceeded.
B
it 15, Thermal warning:
Bit 15 = "0" means that the timers for motor thermal
protection and VLT thermal protection, respectively,
have not exceeded 100%. Bit 15 = "1" means that
one of the timers has exceeded 100%.
B
us reference value:
The frequency reference value is transmitted to the
frequency converter in the form of a 16-bit word. The
value is transmitted as a whole number (0-32767).
16384 (4000 Hex) corresponds to 100%. (Negative
figures are formed by means of 2s complement.)
The bus reference has the following format:
Parameter 203 = "0"
"ref
MIN
-ref
MAX
"
0-16384 (4000 Hex) ~ 0-100% ~ ref
MIN
-ref
MAX
Parameter 203 = "1"
-ref
MAX
-+ref
MAX
-16384 (...Hex)-+16384 (4000 Hex) ~
-100- +100% ~ -ref
MAX
-+ref
MAX
Actual output frequency
The value of the actual output frequency of the
frequency converter is transmitted in the form
of a 16- bit word. The value is transmitted as
a whole number (0-32767). 16384 (4000 Hex)
corresponds to 100%. (Negative figures are formed
by means of 2s complement).
MG.03.H3.02 - VLT is a registered Danfoss trademark
86

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCM Series and is the answer not in the manual?

Danfoss VLT FCM Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCM Series
CategoryDC Drives
LanguageEnglish

Related product manuals