3.1.7 EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operation of the Ethernet network. Additional EMC information is
available in the FC 200/FC 300 series Design Guide.
NB!
Relevant national and local regulations, for example regarding protective earth connection, must be observed.
The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to
the other. Normally a distance of 200 mm (8 inches) is sufficient, but maintaining the greatest possible distance between the cables is recommended,
especially where cables run in parallel over long distances. When crossing is unavoidable, the Ethernet cable must cross motor and brake resistor cables
at an angle of 90 degrees.
A u tom a tio n Dr iv e
VLT
.
MCA 121 EtherNet/IP 3 How to Install
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
13
3