5.1.7 2-** Brakes
Parameter
Number
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
on Index
Type
2-00 DC Hold Current 50% All set-ups TRUE 0 Uint16
2-01 DC Brake Current 50% All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10 s All set-ups TRUE -1 Uint16
2-04 DC Brake Cut In Speed 0 Hz All set-ups TRUE -1 Uint16
2-10 Brake Function [0] Off All set-ups TRUE - Uint8
2-11 Brake Resistor (Ω) All set-ups TRUE 0 Uint16
2-16 AC Brake, Max current 100% All set-ups TRUE 0 Uint16
2-17 Over-voltage Control [0] Disabled All set-ups TRUE - Uint8
2-20 Release Brake Current 0 A All set-ups TRUE -2 Uint32
2-22 Activate Brake Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
Table 5.10
5.1.8
3-** Reference/Ramps
Parameter
Number
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
on Index
Type
3-00 Reference Range [0] Min to Max All set-ups TRUE - Uint8
3-02 Minimum Reference 0 All set-ups TRUE -3 Int32
3-03 Maximum Reference 50 All set-ups TRUE -3 Int32
3-10 Preset Reference 0% All set-ups TRUE -2 Int16
3-11 Jog Speed [Hz] 5 Hz All set-ups TRUE -1 Uint16
3-12 Catch up/slow Down Value 0% All set-ups TRUE -2 Int16
3-14 Preset Relative Reference 0% All set-ups TRUE -2 Int16
3-15 Reference Resource 1 [1] Analog in 53 All set-ups TRUE - Uint8
3-16 Reference Resource 2 [2] Analog in 60 All set-ups TRUE - Uint8
3-17 Reference Resource 3 [11] Local bus reference All set-ups TRUE - Uint8
3-18
Relative Scaling Reference
Resource [0] No function All set-ups TRUE - Uint8
3-40 Ramp 1 Type [0] Linear All set-ups TRUE - Uint8
3-41 Ramp 1 Ramp up Time 3 s All set-ups TRUE -2 Uint32
3-42 Ramp 1 Ramp Down Time 3 s All set-ups TRUE -2 Uint32
3-50 Ramp 2 Type [0] Linear All set-ups TRUE - Uint8
3-51 Ramp 2 Ramp up Time 3 s All set-ups TRUE -2 Uint32
3-52 Ramp 2 Ramp down Time 3 s All set-ups TRUE -2 Uint32
3-80 Jog Ramp Time 3 s All set-ups TRUE -2 Uint32
3-81 Quick Stop Ramp Time 3 s 1 set-up TRUE -2 Uint32
Table 5.11
Parameter Lists
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark 57
5 5

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals