5.1.7 2-** Brakes
Parameter
Number
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
on Index
Type
2-00 DC Hold Current 50% All set-ups TRUE 0 Uint16
2-01 DC Brake Current 50% All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10 s All set-ups TRUE -1 Uint16
2-04 DC Brake Cut In Speed 0 Hz All set-ups TRUE -1 Uint16
2-10 Brake Function [0] Off All set-ups TRUE - Uint8
2-11 Brake Resistor (Ω) All set-ups TRUE 0 Uint16
2-16 AC Brake, Max current 100% All set-ups TRUE 0 Uint16
2-17 Over-voltage Control [0] Disabled All set-ups TRUE - Uint8
2-20 Release Brake Current 0 A All set-ups TRUE -2 Uint32
2-22 Activate Brake Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
Table 5.10
5.1.8
3-** Reference/Ramps
Parameter
Number
Parameter Description Default Value 2 Setup
Change During
Operation
Conversi
on Index
Type
3-00 Reference Range [0] Min to Max All set-ups TRUE - Uint8
3-02 Minimum Reference 0 All set-ups TRUE -3 Int32
3-03 Maximum Reference 50 All set-ups TRUE -3 Int32
3-10 Preset Reference 0% All set-ups TRUE -2 Int16
3-11 Jog Speed [Hz] 5 Hz All set-ups TRUE -1 Uint16
3-12 Catch up/slow Down Value 0% All set-ups TRUE -2 Int16
3-14 Preset Relative Reference 0% All set-ups TRUE -2 Int16
3-15 Reference Resource 1 [1] Analog in 53 All set-ups TRUE - Uint8
3-16 Reference Resource 2 [2] Analog in 60 All set-ups TRUE - Uint8
3-17 Reference Resource 3 [11] Local bus reference All set-ups TRUE - Uint8
3-18
Relative Scaling Reference
Resource [0] No function All set-ups TRUE - Uint8
3-40 Ramp 1 Type [0] Linear All set-ups TRUE - Uint8
3-41 Ramp 1 Ramp up Time 3 s All set-ups TRUE -2 Uint32
3-42 Ramp 1 Ramp Down Time 3 s All set-ups TRUE -2 Uint32
3-50 Ramp 2 Type [0] Linear All set-ups TRUE - Uint8
3-51 Ramp 2 Ramp up Time 3 s All set-ups TRUE -2 Uint32
3-52 Ramp 2 Ramp down Time 3 s All set-ups TRUE -2 Uint32
3-80 Jog Ramp Time 3 s All set-ups TRUE -2 Uint32
3-81 Quick Stop Ramp Time 3 s 1 set-up TRUE -2 Uint32
Table 5.11
Parameter Lists
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark 57