1.5 Parameter Overview
Parameter Overview
0-** Operation/Display
0-0* Basic Settings
0-03 Regional Settings
*[0] International
[1] US
0-04 Oper. State at Power-up
(Hand)
[0] Resume
*[1] Forced stop, ref=old
[2] Forced stop, ref=0
0-1* Setup Handling
010 Active Setup
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Setup
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00–9,999.00 * 0.00
0-32 Custom Readout Max Scale
0.00–9,999.00 * 100.0
0-4* Keypad
0-40 [Hand on] Key on
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto on] Key on
[0] Disabled
*[1] Enabled
0-5* Copy/Save
050 Copy
*[0] No copy
[1] All to
[2] All from
[3] Size indep. from
0-51 Setup Copy
*[0] No copy
[1] Copy from Setup 1
[2] Copy from Setup 2
[9] Copy from Factory Setup
0-6* Password
0-60 (Main) Menu Password
0–999 *0
0-61 Access to Main/Quick Menu
w/o Password
*[0] Full access
[1] LCP: Read Only
[2] LCP: No Access
1-** Load/Motor
1-0* General Settings
1-00 Configuration Mode
*[0] Speed open-loop
[3] Process
1-01 Motor Control Principle
[0] U/f
*[1] VVC+
1-03 Torque Characteristics
*[0] Constant torque
[2] Automatic Energy Optim.
1-05 Local Mode Configuration
[0] Speed Open-loop
*[2] As config in par. 1-00 1-2*
Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18 kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37 kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.00 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
1-22 Motor Voltage
50–999 V *230–400 V
1-23 Motor Frequency
20–400 Hz *50 Hz
1-24 Motor Current
0.01–100.00 A *Motortype dep.
1-25 Motor Nominal Speed
100–9,999 rpm *Motortype dep.
1-29 Automatic Motor Tuning
(AMT)
*[0] Off
[2] Enable AMT
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance (X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5* Load Indep. Setting
1-50 Motor Magnetization at 0
Speed
0–300% *100%
1-52 Min Speed Norm. Magnet. [Hz]
0.0–10.0 Hz *0.0 Hz
1-55 U/f Characteristic - U
0–999.9 V
1-56 U/f Characteristic - F
0–400 Hz
1-6* Load Depen. Setting
1-60 Low Speed Load Compen-
sation
0–199% *100%
1-61 High Speed Load Compen-
sation
0–199% *100%
1-62 Slip Compensation
-400–399% *100%
1-63 Slip Compensation Time
Constant
0.05–5.00 s * 0.10 s
1-7* Start Adjustments
1-71 Start Delay
0.0–10.0 s * 0.0 s
1-72 Start Function
[0] DC Hold/delay time
[1] DC brake/delay time
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at Stop
[Hz]
0.0–20.0 Hz * 0.0 Hz
1-9*Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning
[4] Etr trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0*DC Brake
2-00 DC Hold Current
0–150% * 50%
2-01 DC Brake Current
0–150% * 50%
2-02 DC Braking Time
0.0–60.0 s * 10.0s
2-04 DC Brake Cut In Speed
0.0–400.0 Hz * 0.0 Hz
2-1* Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5–5,000 * 5
2-16 AC Brake, Max current
0–150% * 100%
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00–100.0 A * 0.00 A
2-22 Activate Brake Speed [Hz]
0.0–400.0 Hz * 0.0 Hz
3-** Reference / Ramps
3-0* Reference Limits
3-00 Reference Range
*[0] Min. - Max.
[1] -Max - +Max
3-02 Minimum Reference
-4,999–4,999 * 0.000
3-03 Maximum Reference
-4,999–4,999 * 50.00
3-1* References
3-10 Preset Reference
-100.0–100.0% * 0.00%
3-11 Jog Speed [Hz]
0.0–400.0 Hz * 5.0 Hz
3-12 Catch up/Slow-down Value
0.00–100.0% * 0.00%
3-14 Preset Relative Reference
-100.0–100.0% * 0.00% 3-15
Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Potentiometer
3-18 Relative Scaling Ref. Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp-up Time
0.05–3,600 s * 3.00 s (10.00 s
1)
)
3-42 Ramp 1 Ramp-down Time
0.05–3,600 s * 3.00s (10.00s
1)
)
3-5* Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp-up Time
0.05–3,600 s * 3.00 s (10.00 s
1)
)
3-52 Ramp 2 Ramp-down Time
0.05–3,600 s * 3.00 s (10.00 s
1)
)
3-8* Other Ramps
3-80 Jog Ramp Time
0.05–3,600 s * 3.00 s (10.00s
1)
)
3-81 Quick Stop Ramp Time
0.05–3,600 s * 3.00 s (10.00s
1)
)
4-** Limits/Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
*[0] Clockwise If Par. 1-00 is set to
close-loop control
1)
M4 and M5 only
Table 1.8
Quick Guide
VLT
®
Micro Drive Quick Guide
MG02B722 - VLT
®
is a registered Danfoss trademark 1-11
1 1

Other manuals for Danfoss VLT Micro Drive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive and is the answer not in the manual?

Danfoss VLT Micro Drive Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive
CategoryDC Drives
LanguageEnglish

Related product manuals