7.1.6 SLC
Parameters
FC
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
R1
12
13
18
19
27
29
32
33
50
53
54
55
42
01
02
03
130BE211.11
+24 V
Function Setting
Parameter 4-30
Motor Feedback
Loss Function
[1] Warning
Parameter 4-31
Motor Feedback
Speed Error
50
Parameter 4-32
Motor Feedback
Loss Timeout
5 s
Parameter 7-00 S
peed PID
Feedback Source
[1] 24V
encoder
Parameter 5-70 T
erm 32/33 Pulses
Per Revolution
1024*
Parameter 13-00
SL Controller
Mode
[1] On
Parameter 13-01
Start Event
[19] Warning
Parameter 13-02
Stop Event
[44] Reset key
Parameter 13-10
Comparator
Operand
[21] Warning
no.
Parameter 13-11
Comparator
Operator
*[1] ≈
Parameter 13-12
Comparator
Value
61
Parameter 13-51
SL Controller
Event
[22]
Comparator 0
Parameter 13-52
SL Controller
Action
[32] Set
digital out A
low
Parameter 5-40 F
unction Relay
[80] SL digital
output A
* = Default value
Notes/comments:
If the limit in the feedback
monitor is exceeded, warning
61 feedback monitor is issued.
The SLC monitors warning 61
feedback monitor. If warning 61
feedback monitor becomes true,
relay 1 is triggered.
External equipment could
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the adjustable frequency
drive continues and the
warning disappears. But relay 1
persists until
[O/Reset] is
pressed.
Table 7.9 Using SLC to Set a Relay
Application Examples Instruction Manual
MG07A122 Danfoss A/S © 11/2015 All rights reserved. 41
7 7