3.5.3 CHARGE FAIL INPUT
Minimum voltage 0V
Maximum voltage 35V (plant supply)
Resolution 0.2V
Accuracy ± 1% of max measured voltage
Excitation Active circuit constant power output
Output Power 2.5W Nominal @12V and 24V
Current at 12V 210mA
Current at 24V 10mA
3.5.4 MAGNETIC PICKUP
Type Differential input
Minimum voltage 0.5V RMS
Max common mode
voltage
±2V
Maximum voltage Clamped to ±70V by transient suppressers, dissipation not to exceed 1W.
Maximum frequency 10,000Hz
Resolution 6.25 RPM
Accuracy ±25 RPM
Flywheel teeth 10 to 500
3.6 OUTPUTS
3.6.1 OUTPUTS A & B
Type Normally used for Fuel / Start outputs. Fully configurable for other purposes if the
module is configured to control an electronic engine. Supplied from Emergency Stop
terminal 3.
Rating 15A @ 35V
3.6.2 OUTPUTS C & D
Type Voltage free relays, fully configurable, normally used for generator / mains load switch
control.
Rating 8A @ 250 V AC
3.6.3 OUTPUTS E,F,G & H
Type Fully configurable, supplied from DC supply terminal 2.
Rating 3A @ 35V