EasyManuals Logo
Home>DEEP SEA ELECTRONICS>Control Unit>DSECONTROL DSE7000 Series

DEEP SEA ELECTRONICS DSECONTROL DSE7000 Series User Manual

DEEP SEA ELECTRONICS DSECONTROL DSE7000 Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
DSE Model 7000 Series Control and Instrumentation System Operators Manual
54
Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 2 02/05/2008 ADM
6.3 TEST MODE OF OPERATION
NOTE:- Test Mode is only applicable to DSE7220/DSE7320 controllers.
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Test mode will start the set and transfer the load to the generator to provide a Test on load function.
6.3.1 WAITING IN TEST MODE
When in test mode, the set will not start automatically.
To begin the starting sequence, press the
button.
6.3.2 STARTING SEQUENCE
The set begins to crank.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command via
CAN.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration
after which the next start attempt is made. Should this sequence continue beyond the set number of attempts, the
start sequence will be terminated and the display shows Fail to Start.
When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be derived from the
main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel
(Selected by PC using the 7000 series configuration software).
Additionally, rising oil pressure can be used disconnect the starter motor (but cannot detect underspeed or
overspeed).
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DEEP SEA ELECTRONICS DSECONTROL DSE7000 Series and is the answer not in the manual?

DEEP SEA ELECTRONICS DSECONTROL DSE7000 Series Specifications

General IconGeneral
BrandDEEP SEA ELECTRONICS
ModelDSECONTROL DSE7000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals